Identifier Relative
address
Absolute
address
Character
Name
R/W
Description
□MD
0028h
40041
Control mode setting
R/W R/W the control mode setting
Control execution: 00000
Manual control: 00001
Control stop: 00002
Auto-tuning in progress: 00003
CNT
002Ah
40043
Selection of control type setting
R/W R/W the control type setting
DIR
002Ch
40045
Change of normal or reverse
R/W R/W the forward/reverse operation
switchover setting
MV1
002Eh
40047
Manipulated value
for output 1
R/W R/W the output 1 operation amount
TUN
0030h
40049
Set for PID tuning type
R/W R/W the tuning type setting
ATG
0032h
40051
AT coefficient setting
R/W R/W the AT factor
ATC
0034h
40053
AT sensitivity setting
R/W R/W the AT sensitivity
□P1
0036h
40055
Proportional band setting
for output 1
R/W R/W the output 1 proportional band setting
□I1
0038h
40057
Integral time setting
R/W R/W the integral time setting
□D1
003Ah
40059
Derivative time setting
R/W R/W the derivative time setting
□T1
003Ch
40061
Proportional cycle setting
For output 1
R/W R/W the output 1 proportional frequency
setting
ARW
003Eh
40063
ARW(Anti-reset windup) setting
R/W R/W the anti-reset windup
MH1
0040h
40065
High limit setting of manipulated
value for output 1
R/W R/W the amount-of-operation limiter upper
limit setting
ML1
0042h
40067
Low limit setting of manipulated
value for output 1
R/W R/W the amount-of-operation limiter lower
limit setting
□C1
0044h
40069
Control sensitivity setting
for output 1
R/W R/W the output 1 control sensitivity setting
CP1
0046h
40071
OFF position setting for output 1
R/W R/W the output 1 off-point position setting
MV2
0048h
40073
Manipulated value for output 2
R/W R/W the output 2 operation amount
□P2
004Ah
40075
Proportional band setting
for output 2
R/W R/W the output 2 proportional band setting
□T2
004Ch
40077
Proportional cycle setting for
output 2
R/W R/W the output 2 proportional frequency
setting
MH2
004Eh
40079
High limit setting of manipulated
value for output 2
R/W R/W the amount-of-operation limiter upper
limit setting
ML2
0050h
40081
Low limit setting of manipulated
value for output 2
R/W R/W the amount-of-operation limiter lower
limit setting
□C2
0052h
40083
Control sensitivity setting
for output 2
R/W R/W the output 2 control sensitivity setting
CP2
0054h
40085
OFF position setting
for output 2
R/W R/W the output 2 off-point position setting
PBB
0056h
40087
Manual reset setting
R/W R/W the manual reset
□DB
0058h
40089
Dead band setting
R/W R/W the dead band setting
RP1
005Ah
40091
SV Ramp variation setting
R/W R/W the SV lamp time setting
RP2
005Ch
40093
SV2 Ramp variation setting
R/W R/W the SV2 lamp time setting
E1F
005Eh
40095
Function setting for EV1
R/W R/W the PV event output 1 function setting
E1H
0060h
40097
High limit setting for EV1
R/W R/W the event output 1 upper limit setting
E1L
0062h
40099
Low limit setting for EV1
R/W R/W the event output 1 lower limit setting
E1C
0064h
40101
Control sensitivity setting
for EV1
R/W R/W the event output 1 sensitivity setting
E1T
0066h
40103
Delay time setting for EV1
R/W R/W the event output 1 delay timer setting