6.9 Composition of ASCII response messages
(transmitted from this product to a high-level computer)
For the codes a) through g), see "6.10 Description of ASCII codes."
6.9.1 Response message for a read request message
a) Start code
“:”
b) Slave address
“1” , “B”
c) Function code
“0” , “3”
h) Number of data items
“0” , “4”
Number of registers 2
i)
Data for the first register
(a low-level word)
High level
“0” , “3”
③
When writing ①, ②, ③, and ④
H in the data, write them in the
order described on the left-hand
side. (① represents 1 byte.)
Low level
“0” , “9”
④
Data for the first register + 1
(a high-level word)
High level
“0” , “0”
①
Low level
“0” , “0”
②
f) LRC
“D” , “2”
g) End code
CR, LF
6.9.2 Response message for a write/store request message
a) Start code
“:”
b) Slave address
“0” , “3”
c) Function code
“1” , “0”
d) Register address
High level
“0” , “0”
First register address
Low level
“0” , “0”
e) Number of registers
High level
“0” , “0”
Fixed at 2
Low level
“0” , “2”
f) LRC
“E” , “B”
g) End code
CR, LF
6.9.3 Response message in the case of an error
a) Start code
“:”
b) Slave address
“1” , “B”
h) Function code
“8” , “3”
In the case of an error, the function
code for the request message + 80H is
entered.
j) Error code
“0” , “2”
f) LRC
“6” , “0”
g) End code
CR, LF