TOHO ELECTRONICS TTM000 User Manual
Page 31

31
i) Data portion
This specifies data to be written in the register. The data is fixed at 4 bytes. This product
will write data without the decimal point.
Example: In the case of numerical data
Example
Significance of the value
Proportional band (P) = 1.0 %
0 0 0 0 0 0 0 A H
PV = 1200.0 C
0 0 0 0 2 E E 0 H
SV = -10.00 C
F F F F FC 1 8 H
Example: In the case of text data, write the ASCII code "□" (□ is a space)
Content of Communication
HEX Data
Priority Screen 0-1 = □INP
20494E50H
Priority Screen 0-2 = □MV1
204D5631H
Priority Screen 0-3 = □□P1
20205031H
j) Error code
If a message from a high-level computer is error-ridden, it will be incorporated in the
"response message" from this product and returned.
The error number "04" is an instrument error (memory error or A/D conversion error, AT
error). It will be incorporated in the "response message" regardless of whether there is an
error in the "request message."
If there are two or more errors occurring at the same time, the largest error number will be
incorporated.
The table below indicates the error contents and classifications.
Error No.
Error contents in the "request message" received by this product
01
Received an unsupported function code.
02
Received an address other than the specified one.
03
The numerical data deviated from the "range of settings designated specifically with
setting items."
04
Instrument error (memory error or A/D conversion error, AT error)