beautypg.com

Water connections, Pressure relief valve – State GTS-110-NI User Manual

Page 20

background image

Installation 

20

Page

 

Do  not  use  this  water  heater  if  any  part  has  been  submersed  under  water. 
Immediately call a licensed professional to inspect the water heater to replace 
any damaged parts. 

Do not reverse the hot outlet and cold inlet connections to the water heater.  
This will not properly activate the water heater. 

WATER CONNECTIONS 







All pipes, pipe fittings, valves and other components, including soldering materials, must be suitable for 
potable water systems.  

1.

A manual shut off valve must be installed on the cold water inlet to the water heater between 
the main water supply line and the water heater.  

2.

In  addition,  a  manual  shut  off  valve  is  also 
recommended  on  the  hot  water  outlet  of  the 
unit.  If  the  water  heater  is  installed  within,  or 
subjected  to,  a  closed  loop  water  system,  a 
thermal expansion tank must be installed.  

3.

Before  installing  the  water  heater,  flush  the 
water  line  to  remove  all  debris,  and  after 
installation is complete, purge the air from the 
line.  Failure to do so may cause damage to the 
heater.  

4.

There is a wire mesh filter within the cold inlet 
to  trap  debris  from  entering  your  heater.  This 
will need to be cleaned periodically to maintain 
optimum flow.  

‐Pressure relief valve‐ 

The water heater has a high‐temperature shut off switch built in as a standard safety feature (called a 
Hi‐Limit switch) therefore a “pressure only” relief valve is required. 

 This unit does not come with an approved pressure relief valve.  
 An approved pressure relief valve must be installed on the hot water outlet.  
 The pressure relief valve must conform to ANSI Z21.22 or CAN 1‐4.4 and installation must follow    

local code.  

 The  discharge  capacity  must  be  at  least  140,000  BTU/h  for  the  110  (T‐KJr2)  models,  190,000 

BTU/h for the 310 (T‐K4) models, and 199,000 BTU/h for the 510 (T‐D2) models.  

 The pressure relief valve needs to be rated for a maximum of 150 psi. 
 The discharge piping for the pressure relief valve must be directed so that the hot water cannot 

splash on anyone or on nearby equipment.  

 Attach the discharge tube to the pressure relief valve and run the end of the tube to within 6" 

from  the  floor.  This  discharge  tube  must  allow  free  and  complete  drainage  without  any 
restrictions. 

 If the pressure relief valve installed on the water heater discharges periodically, this may be due 

to a defective thermal expansion tank or defective pressure relief valve.  

 The pressure relief valve must be manually operated periodically to check for correct operation. 
 No valve must be placed between the relief valve and the water heater. 

Pressure  
Relief Valve 

Hot  

outlet 

Cold 
inlet 

Gas 
inlet

As Close as

Possible

CAUTION 

This manual is related to the following products: