4.0 CONFIGURATION

Range Selection Switch: The unit is set to the highest range when calibrated at the factory. To select the other ranges,

slide the switch to the right. Important: Push “zero” button after installing the Model 231RS, and after changing

range.

Auto Zero Button: Press and hold the “ZERO” push-button for 2 seconds to automatically reset zero or provide contact

closure on “Remote Zero, see figure 4 and figure 5. Sensors must be vented to atmosphere.

Electrical Output: The unit is set at the factory to 4-20 mA. To select another output, move the slide switch to the

right. Push the “Zero” button after changing the electrical output mode. Sensors must be vented to atmosphere.

Electrical Connections: Electrical termination for power supply, 3-wire voltage output and 2-wire true 4-20 mA cur-

rent output, and remote zero wiring.

BAR/PSI: Jumper selectable engineering units in Bar ranges or PSI.

A. REV/NORM:

A.REV: Analog Reverse: When in reverse mode, the output increases when the differential pressure decreases and

decreases as pressure increases.

NORM: When in Normal mode output increases as pressure increases and decreases as pressure decreases.

SLOW/FAST: When Slow mode is selected, 5-second averaging is provided for surge damping.

BI-DIR/UNI-DIR: Select UNI-Directional or BI-Directional mode.

Unidirectional mode measures from 0 to full scale differential pressure.

Bidirectional mode measures pressure from minus 1/2 of full scale to plus 1/2 of full scale differential pressure. Output

will read 1/2 full scale when differential pressure is zero.

SWAP/NORM: Jumper selectable Port Swap feature eliminates costly re-plumbing when incorrectly installed or re-

placed. Go from NORMAL to SWAP and the jumper makes the “HI” Port “LO” and the “LO” port “HI.

High Pressure Electrical Terminals (HI): High pressure sensor termination.

Low Pressure Electrical Terminals (LO): Low pressure sensor termination.