Lightning protection


Cabling in areas with a risk of lightning requires a lightning protection. For cabling underground in between
buildings, we recommend the use of special fiber optic cables. If this is not possible, use copper cables that
are suitable for underground installation.

6.2 Cable grip and cable specifications

The HF62 is supplied either with one M16 sealing cable grip or with a ½” conduit adapter. The M16 cable grip
provides effective sealing only with cables having the proper outside diameter. Preferably, use a cable with an
outside diameter of 6 to 7 mm (0.236 to 0.275 inch) with 18 AWG wires.

6.3 Wiring

6.3.1

HF62 standard: 2 x 2-wire, loop powered transmitter


Electrical diagram


The maximum permissible cable length
connecting the HF62 to other devices is
determined by the total resistance resulting
from the addition of the cable resistance and
that of the devices connected in series with
the unit. On each circuit, this resistance
should not exceed 500 ohms.





Terminal block diagram

Terminals

Description

K1-1: H-OUT

Relative humidity or dew point (+)
OUT-1

K1-2: V+

Power supply: 10…28 VDC (+)

Terminals

Description

K2-1: T-OUT

Temperature output (+)
OUT-2

K2-2: V+

Power supply: 10…28 VDC (+)



Note:

connect the + of the power supply to each of the V+ terminals (K1-1 and K2-1). These terminals are not

internally connected.