Character

Name, Description, Setting range

Initial value

PV filter time constant setting

Sets the

PV filter time constant.

If the setting value is too large, it affects control result due to

the response delay.

0.0 to 10.0 seconds

0.0 seconds

Control output high limit setting

Sets the control output high limit value.
This setting item is not indicated when

ON/OFF action.

Control output low limit

to 105%

Setting greater than 100% is effective to DC current output type

100%

Control output low limit setting

Sets the control output low limit value.
This

setting item is not indicated during ON/OFF action.

-5% to control output high limit

Setting less than 0% is effective to DC current output type.

0%

Control output ON/OFF action hysteresis setting

Sets the

ON/OFF action hysteresis for the control output.

This setting item is indicated only for ON/OFF action (P=0)

Thermocouple and RTD input: 0.1 to 100.0°C (°F)

DC voltage and current input: 1 to 1000
(Decimal point place follows the selection.)

1.0°C

Alarm action selection

Selects alarm action type.

No alarm

:

High limit alarm

:

Low limit alarm

:

High/Low limits alarm

:

High/Low limit range alarm

:

Process high alarm

:

Process low alarm

:

High limit alarm w/standby

:

Low limit alarm w/standby

:

High/Low limits alarm w/standby :

No alarm

Alarm action Energized/Deenergized

Selects alarm action Energized/Deenergized.

This setting item is not indicated when “No alarm” action is

selected in [Alarm action selection].

Energized:

Deenergized:

Energized

Alarm HOLD function selection

Selects whether alarm HOLD function is [Used] or not.

If alarm HOLD function is set to used, once the alarm
functions alarm output remains until the power is turned off.

This setting item is not indicated when “No alarm” action is

selected in [Alarm action selection].

Alarm

HOLD [Not used]:

Alarm

HOLD

[Used]

:

Alarm HOLD
[Not used]

Alarm hysteresis setting

Sets the alarm hysteresis.

This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].

Thermocouple and RTD input

: 0.1 to 100.0°C (°F)

DC voltage and DC current input: 1 to 1000 (Decimal point
place follows the selection.)

1.0°C