3.2 Main setting mode

Character

Name, Description, Setting range

Initial value

Main setting

Set the value for controlled objects.

Scaling low limit setting value to Scaling high limit setting value

(Decimal point place follows the selection for DC current input)

0° C

3.3 Sub setting mode

Character

Name, Description, Setting range

Initial value

PID auto-tuning Perform/Cancel

Performs

PID auto-tuning. However when PID auto-tuning does

not finish after 4 hours it started, PID auto-tuning is shut down
compulsory.

PID cancellation

:

PID auto-tuning performing:

Proportional band setting

Sets the p

roportional band.

ON/OFF action when setting the value to 0.0

0.0 to 110.0%

2.5%

Integral time setting

Sets the

integral time.

Setting the value to 0 disables this function.

This

setting item is not indicated for ON/OFF action.

0 to 1000 seconds

200 seconds

Derivative time setting

Sets the derivative time.

Setting the value to 0 disables this function.

This

setting item is not indicated for ON/OFF action.

0 to 300 seconds

50 seconds

Anti-reset windup setting

Sets

anti-reset windup.

Setting the value to 0 disables this function.

This

setting item is indicated only for PID action.

0 to 100%

50%

Proportional cycle setting

Sets the proportional cycle value for the control output

(OUT).

This

setting item is not indicated for ON/OFF action or DC

current output.

1 to 120 seconds

Relay: 30 Sec.
Solid State: 3 Sec.

Manual reset setting

Sets the resetting value manually.
This

setting item is indicated only for P and PD action.

Proportional band converted value (In the case of DC voltage

and current input, decimal point place follows the selection.)

0.0

Alarm setting

Sets the action point for the alarm output.

Setting the value to 0 or 0.0 disables this function.
(excluding Process high and Process low alarm)

When Loop break alarm and Heater burnout alarm are applied
together, the output is common.

This setting item is not indicated when “No alarm” action is

selected in [Alarm action selection].

See (Table 3.3-1). (In the case of DC voltage and DC current
input, decimal point place follows the selection.)

0° C