Dwyer SCZ10 User Manual
Page 4

3.2 Main setting mode
Character
Name, Description, Setting range
Initial value
Main setting
• Set the value for controlled objects.
•
Scaling low limit setting value to Scaling high limit setting value
(Decimal point place follows the selection for DC current input)
0° C
3.3 Sub setting mode
Character
Name, Description, Setting range
Initial value
PID auto-tuning Perform/Cancel
• Performs
PID auto-tuning. However when PID auto-tuning does
not finish after 4 hours it started, PID auto-tuning is shut down
compulsory.
•
PID cancellation
:
PID auto-tuning performing:
Proportional band setting
• Sets the p
roportional band.
•
ON/OFF action when setting the value to 0.0
•
0.0 to 110.0%
2.5%
Integral time setting
• Sets the
integral time.
•
Setting the value to 0 disables this function.
• This
setting item is not indicated for ON/OFF action.
•
0 to 1000 seconds
200 seconds
Derivative time setting
• Sets the derivative time.
•
Setting the value to 0 disables this function.
• This
setting item is not indicated for ON/OFF action.
•
0 to 300 seconds
50 seconds
Anti-reset windup setting
• Sets
anti-reset windup.
•
Setting the value to 0 disables this function.
• This
setting item is indicated only for PID action.
•
0 to 100%
50%
Proportional cycle setting
• Sets the proportional cycle value for the control output
(OUT).
• This
setting item is not indicated for ON/OFF action or DC
current output.
•
1 to 120 seconds
Relay: 30 Sec.
Solid State: 3 Sec.
Manual reset setting
• Sets the resetting value manually.
• This
setting item is indicated only for P and PD action.
•
Proportional band converted value (In the case of DC voltage
and current input, decimal point place follows the selection.)
0.0
Alarm setting
• Sets the action point for the alarm output.
•
Setting the value to 0 or 0.0 disables this function.
(excluding Process high and Process low alarm)
When Loop break alarm and Heater burnout alarm are applied
together, the output is common.
•
This setting item is not indicated when “No alarm” action is
selected in [Alarm action selection].
•
See (Table 3.3-1). (In the case of DC voltage and DC current
input, decimal point place follows the selection.)
0° C