8. PID auto-tuning of the SCZ10
In order to decide each P, I, D value and ARW automatically, this system gives a fluctuation
to the controlled object to get a optimal value.
3 types of fluctuation below are automatically selected.
[ When the difference between setting value and processing temperature is large in rising]
When AT bias is set to 20°C(°F)), a fluctuation is given at the temperature 20°C(°F
[When control is stable]
A fluctuation is given at the setting value.
[ When the difference between the setting value and processing temperature is large when
temperature falls]
When AT bias is set to 20°C(°F), a fluctuation is given at the temperature 20°C(°F)
(
higher than the
Setting
value
Temp.
Time
AT
(1)
(2)
(3)
Temperature 20
°C(°F)
lower
than the setting value
(4)
:
AT
Auto-tuning starting point
Calculating PID constant
PID contatnt calculated
Controlled by the PID
constant set by auto-tuning.