Input Thermocouple: K, J, R, S, E, T, N, PL-II, C (W/Re5-26) External resistance: 100

Ω or less

B thermocouple: External resistance: 40

Ω or less

RTD

: Pt100, JPt100 3-wire system

Allowable input wire resistance (10

Ω or less per wire)

DC current

: 0 to 20mAdc, 4 to 20mA input impedance 50

Ω

[Connect 50

Ω shunt resistor (sold separately) between input terminal (5) and (6).]

Allowable input current: 50mA or less

DC voltage

: 0 to 1Vdc

Input impedance: 1M

Ω or greater

Allowable input voltage: 5V or less
Allowable signal source resistance

: 2k

Ω or less

Accuracy (Indicating

Setting)

Thermocouple input: Within ±0.2% of input span ±1 digit or ±2°C (4°F) whichever is greater.

R, S input 0 to 200°C (0 to 400°F): Within ±6°C (2°F).

B input 0 to 300°C (0 to 600°F): Accuracy is not guaranteed.

RTD input: Within ±0.1% of input span ±1 digit or within ±1°C (2°F) whichever is greater.

DC voltage input

: Within ±0.2% of input span ±1 digit

DC current input

: Within ±0.2% of input span ±1 digit

Input sampling period

: 0.25 seconds

Control Control action

PID action (with auto-tuning function)

PI action

: When derivative time is set to 0

PD action (with manual reset function): When integral time is set to 0

P action (with manual reset function)

: When derivative and integral time are set to 0

ON/OFF action

: When proportional band is set to 0

Proportional band: 0.0 to 110.0% [Factory adjusted as 2.5%]

(ON/OFF action when set to 0.0)

Integral time

: 0 to 1000 seconds (Off when set to 0) [Factory adjusted as 200 seconds]

Derivative time

: 0 to 300 seconds (Off when set to 0)[Factory adjusted as 50 seconds]

Proportional cycle

: 1 to 120 seconds [Factory adjusted as Relay: 3/ sec.; SS: 3 sec.]

ARW

: 0 to 100% [Factory adjusted as 50%]

Manual reset

: ±Proportional band converted value [Factory adjusted as 0.0]

Output limit

: 0 to 100% (DC current output type: -5 to 105%)

(Not available for ON/OFF action)
[Factory adjusted as control output low limit setting value 0%
control output high limit setting value100%]

Hysteresis

: Thermocouple and RTD input: 0.1 to 100.0°C (°F)

[Factory adjusted as 1.0°C]
DC voltage and current input: 1 to 1000
(Decimal point place follows the selection.)
[Factory adjusted as 10]

Control output (OUT)

Relay contact

: Control capacity 250Vac 3A (Resistive load)

250Vac 1A (Inductive load COS

φ = 0.4)

Electric life 100,000 cycles

Non-contact voltage

(for SSR drive): 12

--
--

Vdc Max. 40mA (Short-circuit protected)

DC current

: 4 to 20mAdc, Load resistance: Max. 550

Ω

Output accuracy: Within ±0.3% of output span
Resolution

: 12000

Alarm Alarm (EVT) output (Common output with Loop break alarm, Heater burnout

alarm [optional])

When input exceeds the range in ± deviation setting (excluding Process alarm) to the main

setting, alarm (EVT) turns ON or OFF (High/Low limit range alarm), and when Deenergized
is selected in Energized/Deenergized selection, alarm (EVT) is activated conversely.