SETTING SET POINTS AND ALARMS

The hot key provides direct access to the Set Point and Alarm MENU. The Set
Point and Alarm MENUS that are displayed are based upon the Control (CtrL) SUB
MENU.

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

SP/AL

Visible when

Visible when

Visible when

Visible when

Visible when

Visible when

mode =

mode =

mode =

mode =

mode =

mode =

CONTROL MODE

CONTROL MODE

CONTROL MODE

CONTROL MODE

CONTROL MODE

CONTROL MODE

SET POINT ADJUSTMENT
Adjusting the DH

®

3 Set Points is quick and simple. Instead of setting a set point and dead-

band, simply adjust

SP1H

or

SP2H

for the desired relay turn on point, and then adjust

SP1L

or

SP2L

for the desired relay turn off point.

PRESSURE

PRESSURE

0

0

0

0

TIME

TIME

0.2

0.2

0.4

0.4

0.6

0.6

0.8

0.8

1.0

(in. w.c.)

In the above graph, an instrument with a 1.0˝ range would have the SP1 relay turn on at
0.8˝ and off at 0.4˝.

SP1H

sets the relay turn on point, and

SP1L

sets the relay turn off point.

The relays outputs normally function in the direct acting mode, which means the relays turn
on with an increase in pressure. SP1 may be configured to act as a reverse acting relay
(refer to the 1SP SUB MENU setting, page 15). When set for reverse acting,

SP1H

sets the

relay turn OFF point, and

SP1L

sets the relay turn ON point. SP2 is always direct acting.