(Resolution) SUB MENU

The DH 3 is capable of displaying four digits of resolution. However, at very low
pressures the instability of the pressure may cause fluctuations in the least
significant digit causing the least significant digit to be of little value.
Three digit resolution (

3DIG

) can only be active when there is at least one digit to the

right of a decimal.

3DIG

- Set display for 3 digit resolution

4DIG

- Set display for 4 digit resolution

Pd.S

(Process Display) SUB MENU

STD

- Display reads pressure, velocity, or flow values

PCT

- Display reads % of full scale value

When the display is reading percent,

PCT

is displayed in the upper right of the

display. The percent display is only available in pressure operation.

DAMP

(Dampening) SUB MENU

Adjust from 1-16

Dampening stabilizes the display from instabilities due to things such as vibration and
excessive pressure fluctuations. The dampening setting adjusts the amount of
readings that are averaged for each display update. Adjust the dampening value until
the display reads a stable value for the application.

AdU

(Advanced) MAIN MENU

POL

- Process output low

ZERO

- Zero calibration

POH

- Process output high

SPAN

- Span calibration

MSP1

- Maintenance set point 1

MSP2

- Maintenance set point 2

POL

and

POH

(Process Output Low and High) SUB MENUS

This feature is used in pressure operation only.

Process output low and high are used to scale the 4-20 mA output. Set

POL

to the

desired display reading for 4mA output, and set

POH

to the desired display reading

for 20 mA output.

POH

must be higher than

POL

.

POL

may be adjusted 2% BELOW

minimum scale up to

POH

.

POH

may be adjusted from

POL

to 2% ABOVE maximum

scale.