Dwyer instruments, inc – Dwyer DH3 User Manual
Page 20
MSP1
and
MSP2
(Maintenance Set Point 1 & 2) SUB MENUS
Adjust for the desired maintenance set points when the unit is placed in the
maintenance mode. The deadband is fixed at 2% of full scale. To enter or
leave the maintenance mode, press and hold the for 8 seconds.
ZERO
and
SPAN
(Calibration of Zero and Span) SUB MENUS
The lower display reads
CAL
in this mode.
ZERO
Calibration
NOTE: For accurate calibration, DO NOT apply any pressure when
performing this function.
With the display reading
ZERO
, press the ENTER key. The upper display will
blink. Press ENTER again to complete the zeroing of the instrument or press
the
MENU
key to cancel.
SPAN
Calibration
With the display set to
SPAN
, apply full scale pressure to the unit. Press the
ENTER key. The upper display will blink. Press ENTER again to complete the
calibration or press the
MENU
key to cancel.
SP/AL
SP/AL
©Copyright 2012 Dwyer Instruments, Inc.
Printed in U.S.A. 2/12
FR# 443555-00 Rev.3
DWYER INSTRUMENTS, INC.
Phone: 219/879-8000 www.dwyer-inst.com
P.O. BOX 373 • MICHIGAN CITY, IN 46360, U.S.A.
Fax: 219/872-9057 e-mail: [email protected]