Dwyer DH3 User Manual
Page 14
![background image](/manuals/371619/14/background.png)
14
FLO
(Flow) SUB MENU
For flow measurements the following units are available:
SCFM
- Standard cubic feet per minute
M^3H
- Cubic meters per hour
FLO r
(Flow Range) SUB MENU
LO
- 99.99 x 1K flow range
HI
- 999.9 x 1K flow range
Tables 3-6 show the flow ranges available, and the maximum duct size that can be set
for each input range.
Table 3
FLOr
=
LO
Maximum Duct Size (English)
RANGE
IN WC
0.1
0.25
0.5
1
2.5
5
10
25
SCFM
RANGE
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
MAX. DUCT
SIZE, SQ.
FT.
78.9
49.9
35.3
24.9
15.7
11.1
7.8
4.9
KFAC
SUB MENU
KFAC
K Factor - becomes accessible if the instrument is set for Velocity or Flow.
When the DH3
®
is used with a Pitot tube, the manufacturer may specify a K
Factor. The adjustment range is 0.01 to 2.00. The factory setting is 1.
Table 4
FLOr
=
HI
Maximum Duct Size (English)
RANGE
IN WC
0.1
0.25
0.5
1
2.5
5
10
25
SCFM
RANGE
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
MAX. DUCT
SIZE, SQ.
FT.
789.8
499.5
353.1
249.7
157.9
111.7
78.9
49.9
Table 5
FLOr
=
LO
Maximum Duct Size (Metric)
RANGE
IN WC
0.1
0.25
0.5
1
2.5
5
10
25
Mˆ3/Hr
RANGE
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
99.99 x 1K
MAX. DUCT
SIZE Mˆ2
4.32
2.73
1.93
1.37
0.86
0.61
0.43
0.27
Table 6
FLOr
=
HI
Maximum Duct Size (Metric)
RANGE
IN WC
0.1
0.25
0.5
1
2.5
5
10
25
M
3
/Hr
Range
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
999.9 x 1K
MAX. DUCT
SIZE, M
2
43.19
27.31
19.3
13.64
8.63
6.10
4.31
2.73