The following alarm function SUB MENUS are activated when

CtrL

is set to

SPAL

:

AL

(Alarm Type) SUB MENU

HI

- High alarm

LO

- Low alarm

HILO

- For a high/low guardband type alarm

ALARM ADJUSTMENT
Alarm settings are dependent upon the selected alarm mode. The DH3

®

differential pres-

sure controller alarm may be configured as a High Alarm, Low Alarm, or High/Low Alarm.
Alarm settings are all absolute and may be set to anywhere within the range of the instru-
ment. The dead bands of the alarms are fixed at 1% of full scale.

MIN. PRESSURE

MAX. PRESSURE

ALHI

Relay OFF Relay ON

HIGH ALARM FUNCTION

MIN. PRESSURE

MAX. PRESSURE

ALLO

Relay ON Relay OFF

LOW ALARM FUNCTION

MIN. PRESSURE

MAX. PRESSURE

ALLO

Relay ON Relay OFF Relay ON

HIGH/LOW ALARM

FUNCTION

ALHI