F-2000, Page 8, Flow range alarm example – Blue-White F-2000 – Solvent Weld PVC Tee Fitting User Manual
Page 8
F-2000
Page 8
Hysteresis
Hysteresis
Flow
High Alarm
Low Alarm
Nominal
Range
FLOW RANGE ALARM EXAMPLE
High setpoint trigger value 250.0 GPM
High setpoint release value 240.0 GPM
Low setpoint release value 160.0 GPM
Low setpoint trigger Value 150.0 GPM
Note:
If the relay flickers on and off due to unstable flow, readjust
the release value to increase the amount of hysteresis.
2.4 Programming the MODEL PC & PB when the setpoints are assigned to rate.
Note: The F-2000 must be powered by the AC Adapter.
Note:
While in the programming mode, if no buttons are pressed within twenty seconds, the programming mode
is automatically exited without saving the input of the last screen.
Step 1
Enter the programming mode and assign the setpoints to the RATE mode.
Step 2
Enter the High Alarm Trigger Value or 0.
! Press for at least 1.25 seconds.
! Press to by-pass the first six program screens until you reach the Rate Setpoint Screen (seventh screen).
! Press to select Rate Setpoint On.
! Press .
! Press to select the digit or decimal point to be modified. The selected digit will blink.
! Press to change the selected digit. Note: Setting the value to zero disables the High Alarm.
! Press when you have entered your desired High Alarm Trigger Value.
ENTER
ENTER
TOTAL
CLEAR
ENTER
CLEAR
SETPOINT
TOTAL
CLEAR
ENTER
O
RATE
SETPOINT
RATE
SETPOINT
00000
Caution: An emergency shut off switch for externally controlled electrical equipment is recommended.