F-2000

Page 15

2.7 Examples of Setpoint Assigned To Batch

Example 1:

Proportional feed application. A chemical feed pump must run for 3 seconds for every 12.57
liters of flow measured.

Example 2:

Manual batch application. In a truck depot, an attendant must open a solenoid valve
allowing 2,000 gallons of water to flow into each truck.

Step 1

Set the SETPOINT MODE SELECTION screen to SETPOINT - BATCH.

Step 2

Set SETPOINT - BATCH - 1 screen for a batch amount value of 000012.57

Step 3

Set SETPOINT - BATCH - 2 screen for automatic batch start.

Step 4

Set SETPOINT - BATCH - 3 screen for external equipment timer on-time of 003 seconds.

Step 5

Wire the pump to the normally open terminals of the relay terminal block.

Step 6

The pump will start automatically when the batch amount is reached.

Step 1

Set the SETPOINT MODE SELECTION screens to SETPOINT - BATCH

Step 2

Set SETPOINT - BATCH - 1 screen for a batch amount value of 00002000

Step 3

Set SETPOINT - BATCH - 2 screen for automatic BATCH START OFF.

Step 4

Set SETPOINT - BATCH - 3 screen for external equipment timer on-time of 000 seconds.

Step 5

Wire the solenoid valve to the normally open terminals of the relay terminal block.

Step 6

Press to begin the first batch.

CLEAR

SETPOINT