F-2000

Page 11

Example 3:

A solenoid valve must open if the flow rate goes above 225 gallons per minute.

Step 1

Set the SETPOINT MODE SELECTION SCREEN] to SETPOINT - RATE.

Step 2

Set SETPOINT - RATE - 1, screen for a high trigger value of 225.

Step 3

Set SETPOINT - RATE - 2, screen for a high release value of less than 225. Example: 220

Step 4

Set SETPOINT - RATE - 3, screen for a low trigger value of 0. (Low alarm not used).

Step 5

Set SETPOINT - RATE - 4, screen for a low release value of 0. (Low alarm not used).

Step 6

Set SETPOINT - RATE - 5, to the desired alarm delay silencer time from 0 - 999 seconds (optional).

Step 7

Wire the value to the normally open terminals of the relay terminal block. See page 16.

Release

220

GPM

Trigger

225

GPM

Open Valve

Flow