Installation – Badger Meter QuikSert User Manual
Page 8
![background image](/manuals/371188/8/background.png)
INSTALLATION
Before installation, the flow meter should be checked internally for foreign material and to be sure that the rotor spins freely .
Gas lines should also be cleared of all debris . The flow meter must be installed with the flow indication arrow, etched on the
exterior of the meter body, pointing in the correct direction of flow . The preferred mounting orientation is to have the meter
installed in horizontal piping, with the pickup facing upward . However, the meter will function in any position .
While the flow meter body and magnetic pickup are sold as separate items, in most instances they are ordered at the same
time and come assembled from the factory . If the magnetic pickup was not ordered with the meter body or replacement of
the magnetic pickup becomes necessary, all that is needed to install it is to thread the pickup into the pickup port until it is
bottomed out . Finger tightening is all that is required for proper installation .
The gas that is to be measured must be free from any large particles that may obstruct the rotor from turning . If particles are
present, a filter of at least 60 mesh (0 .0092 clearance) should be installed upstream before operation of the flow meter .
The preferred plumbing setup is one containing a bypass line (see
) that allows for meter inspection and repair
without interrupting flow . If a bypass line is not used, it is important that all control valves be located downstream of the flow
meter (see
) .
Flow Straightner
(Optional)
Isolation
Valve
Isolation
Valve
QuikSert Turbine
Flow Meter
Display
Bypass Line
5 Pipe Diameters
Minimum
10 Pipe Diameters
Minimum
2
1
Figure 4: Bypass line installation
It is recommended that a minimum length, equal to ten (10) pipe diameters of straight pipe, be installed on the upstream side
and five (5) diameters on the downstream side of the flow meter . Otherwise meter accuracy may be affected . Piping should be
the same size as the flange size . If adequate straight runs of pipe are not available or if erratic flow readings are experienced,
place a bundled-tube flow straightener upstream of the flow meter installation .
5 Pipe Diameters
Minimum
10 Pipe Diameters
Minimum
Isolation
Valve
Display
Flow Straightner
(Optional)
QuikSert Turbine
Flow Meter
2
1
Figure 5: Installation without bypass line
Turbine Flow Meter, B142 Gas QuikSert
Page 8
June 2014