Alicat VC Series Volumetric Flow Controller User Manual

Page 19

background image

19

Select Menu Mode
Pushing “Mode” once will bring up the “Select Menu” display (Figure 7, page 11). Push the button

nearest your selection to go to the corresponding screen. Push “Mode” again to return to the Main

Mode display. (

Note: If your controller was ordered with Totalizing Mode option (page 43), pushing the

“Mode” button once will bring up the “Totalizing Mode” display. Pushing “Mode” a second time will bring

up the “Select Menu” display.)

Control Setup Mode

The Control Setup Mode is accessed by pressing the center button above “Control” on the Select Menu

Display (Fig.7 page 11) This mode allows the user to set up most parameters commonly associated with

PID control. Alicat Scientific flow controllers allow the user to select how the set-point is to be conveyed

to the controller, what that set-point is if control is local, and what the Proportional and Differential terms

of the PID control loop will be. The UP and DOWN buttons for adjusting variables can be held down for

higher speed adjustment or pressed repeatedly for fine adjustment

Select Loop Input

>P 200 >Analog
D 500 Volume Serial
AUT0on

Local

Set 0.00

Control

Up Down Setup

Figure 14. VC Series Control Setup Display

Input – VC Series Flow Controllers normally ship defaulted to analog control as indicated in Figure 14

above. To change how the set-point will be conveyed to the controller push the button in the upper right

hand corner just above the dynamic label “Input” until the arrow is directly in front of the desired option.

The controller will ignore any set-point except that of the selected input and it will remember which input

is selected even if the power is disconnected.

Analog refers to a remote analog set-point applied to Pin 4 of the Mini-DIN connector as described

in the installation section of this manual. To determine what type of analog set-point your controller

was ordered with, refer to the Calibration Data Sheet that was included with your controller. 0-5 Vdc

is standard unless ordered otherwise. Note that if nothing is connected to Pin 4, and the controller is

set for analog control, the set-point will float.

CAUTION! N

ever

leave

a

C

oNtroller

with

aNy

NoN

-

zero

set

-

poiNt

if

No

pressure

is

available

to

make

flow

. t

he

CoNtroller

will

apply

full

power

to

the

valve

iN

aN

attempt

to

reaCh

the

set

-

poiNt

. w

heN

there

is

No

flow

,

this

CaN

make

the

valve

very

hot!