beautypg.com

Alicat VC Series Volumetric Flow Controller User Manual

Page 13

background image

13

Loop—The selection of what variable to close the loop on is a feature unique to these mass flow

controllers. When the mass flow controller is supplied with the control valve upstream of the electronics

portion of the system, the unit can be set to control on outlet pressure (absolute pressures only) or

volumetric flow rate, instead of mass flow rate. Repeatedly pressing the button adjacent to the word

“Loop” on the control setup screen will change what variable is controlled. The change from mass to

volume can usually be accomplished without much, if any, change in the P and D settings. When you

change from controlling flow to controlling pressure, sometimes fairly radical changes must be made

to these variables.

Note: Full scale pressure is normally 160PSIA. Consult the factory if you are having

difficulties with this procedure.
Select – To avoid accidental changing of the PID loop parameters or the set-point, the Control Setup

mode defaults with the selector on a null position. To change the set-point or the P and D PID loop

parameters, push the button in the upper left corner just above the dynamic label “Select” until the

selection arrow is pointing to the parameter you wish to change. When the parameter you wish to

change is selected, it may be adjusted up or down with the buttons under the display below the dynamic

labels “Up” and “Down”. Press the buttons repeatedly to make slow adjustments or hold them down to

make fast adjustments.
P refers to the Proportional term of the PID loop. Before changing this parameter, it is good practice to

write down the initial value so that it can be returned to the factory settings if necessary.
D refers to the Differential term of the PID loop. Before changing this parameter, it is good practice to

write down the initial value so that it can be returned to the factory settings if necessary.
AUT0on / AUT0off refers to the standard auto-tare or “auto-zero” feature. It is recommended that the

controller be left in the default auto-tare ON mode unless your specific application requires that it be

turned off. The auto-tare feature automatically tares (takes the detected signal as zero) the unit when it

receives a zero set-point for more than two seconds. A zero set-point results in the closing of the valve

and a known “no flow” condition. This feature helps to make the device more accurate by periodically

removing any cumulative errors associated with drift.
Set refers to the Set-Point. This parameter may only be changed if “Local” is selected as the Input. See

above for information on selecting the input. Using the UP and DOWN buttons, the set-point may be

adjusted between zero and the full-scale range of the controller.

CAUTION! N

ever

leave

a

C

oNtroller

with

aNy

NoN

-

zero

set

-

poiNt

if

No

pressure

is

available

to

make

flow

. t

he

CoNtroller

will

apply

full

power

to

the

valve

iN

aN

attempt

to

reaCh

the

set

-

poiNt

. w

heN

there

is

No

flow

,

this

CaN

make

the

valve

very

hot!