Ecochill chiller, Cooling line version c motorcondensing – Airedale EcoChill 6kW - 46kW User Manual
Page 34
![background image](/manuals/370939/34/background.png)
34
EcoChill
Chiller
Technical Manual 7300221 V1.1.0_02/2013
COOLING LINES
Model
Line length [m]
Gas line Ø [mm]
Liquid line Ø [mm]
R410A [g/m]
ECL 020 C
0-10
12.7
9.52
70
10-20
12.7
9.52
70
20-30
12.7
9.52
70
ECL 025 C
0-10
12.7
9.52
70
10-20
12.7
9.52
70
20-30
12.7
9.52
70
ECL 030 C
0-10
12.7
12.7
120
10-20
12.7
12.7
120
20-30
15.88
12.7
130
ECL 040 C
0-10
12.7
12.7
120
10-20
15.88
12.7
130
20-30
15.88
12.7
130
ECL 050 C
0-10
15.88
15.88
190
10-20
15.88
15.88
190
20-30
18
15.88
190
ECL 070 C
0-10
15.88
15.88
190
10-20
18
15.88
190
20-30
18
15.88
190
ECL 080 C
0-10
15.88
15.88
190
10-20
18
15.88
190
20-30
22
15.88
210
ECL 090 C
0-10
18
15.88
190
10-20
22
15.88
210
20-30
22
15.88
210
ECL 100 C
0-10
28.00
15.88
230
10-20
28.00
15.88
230
20-30
28.00
15.88
230
ECL 150 C
0-10
28.00
15.88
230
10-20
28.00
15.88
230
20-30
28.00
15.88
230
ECL 200 C
0-10
35.00
15.88
260
10-20
35.00
18.00
310
20-30
35.00
18.00
310
13. COOLING LINE VERSION C
MOTORCONDENSING
If evaporator is placed lower than con-
denser, risers are needed in the riser,
to favour the transporting of oil towards
the compressor. By line length, dis-
tance measured between the units on
the liquid line, is intended. For addition-
al information please contact company.