EcoChill
Chiller
Technical Manual 7300221 V1.1.0_02/2013
COOLING
020C
025C
030C
040C
050C
070C
080C
090C
100C
150C
200C
Cooling capacity
kW
5.70
6.00
7.50
9.60
13.70
16.80
20.80
22.50 26.90 33.40
43.70
Total input power
(°)
kW
1.85
2.05
2.50
3.30
4.10
5.00
6.50
6.80
8.60
10.20
14.10
ENERGYEFFICIENCIES
EER
W/W
3.08
2.93
3.00
2.91
3.34
3.36
3.20
3.31
3.13
3.27
3.10
ELECTRICAL DATA
Total input current
(°)
400V A
3.7
4.2
4.70
6.3
8.9
9.9
12.4
13.1
17.1
19.3
26.4
230V
9.5
10.0
13.0
16.3
N,D,
N,D,
N,D,
N,D,
N,D,
N,D,
N,D,
Maximum current (FLA)
(°)/H
400V A
6
6
6.7
8.7
11.3
13.5
16.3
17.3
22.0
26.0
34.0
230V
16.5
16.5
19.7
23.7
N,D,
N,D,
N,D,
N,D,
N,D,
N,D,
N,D,
Peak current (LRA)
(°)/H
400V A
26.5
32.5
35.7
48.7
65.3
75.3
102.3
96.3
76.0
87.0
117.0
230V
59.5
62.5
83.7
98.7
N,D,
N,D,
N,D,
N,D,
N,D,
N,D,
N,D,
COMPRESSORS (SCROLL)
Number/circuit
n°
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
2/1
2/1
2/1
Input current
A
3.2
3.7
4.0
5.5
7.4
8.4
10.9
11.5
Compressors sump heater
n°xW
1x70
1x70
1x70
1x70
1x35
1x35
1x35
1x65
2X35
2X35
2X65
Capacity controls
%
1-100 1-100 1-100 1-100 1-100 1-100 1-100 1-100
0-50-100 0-50-100 0-50-100
FANS (AXIAL)
Number
n°
1
1
1
1
2
2
2
2
2
2
2
Air flow rate
mc/h
2500
2500
3500
3500
7200
7200
7300
7200
13200
12000
12000
Input power
kW
0.085
0.085
0.14
0.14
0.28
0.28
0.28
0.28
0.6
0.6
0.6
Input current
A
0.45
0.45
0.66
0.66
1.32
1.32
1.32
1.32
2.6
2.6
2.6
REFRIGERANT CHARGE
R410A
Kg
1.250
1.300
1.560
2.00
3.480
3.790
3.730
4.700
COOLING CONNECTIONS
Suction line
Ø
15.88
15.88
15.88
15.88
22
22
22
28
28
28
35
Liquid line
Ø
9.52
9.52
12.7
12.7
15.88
15.88
15.88
15.88
15.88
15.88
15.88
NOISE DATA
Sound power
dB(A)
61.0
61.0
68.0
68.0
69.0
69.0
69.0
68.0
76.0
77.0
78.0
Sound Pressure
dB(A)
30.0
30.0
37.0
37.0
38.0
38.0
38.0
37.0
44.0
45.0
46.0
Nominal conditions reference
IN COOLING MODE
- Evaporation temperature
5 °C
- External air temperature
35 °C
Sound power
Airedale determines sound power values in
agreement with the 9614 Standard, in com-
pliance with that requested by Eurovent certi-
fication.
(1) Sound Pressure
Sound pressure measured in free field condi-
tions with reflective surface (directivity factor
Q=2) at 10mt distance from external surface of
unit, in compliance with ISO 3744 regulations.