Ecochill chiller, Desuperheater – Airedale EcoChill 6kW - 46kW User Manual
Page 33
33
EcoChill
Chiller
Technical Manual 7300221 V1.1.0_02/2013
12. DESUPERHEATER
The heating capacity obtained by
the desuperheater is attained by
multiplying the nominal value (Pd),
given in table 14.1.2. by a relevant
coefficient (Cd).
The diagrams allow to obtain
the corrective coefficients to use
depending on the temperature of the
external air and the temperature of the
water produced at the desuperheater.
NOTE
The use of the desuperheater
is possible in cooling function;
for heat function it must be
intercepted.
12.1. PRESSURE DROPS
All sized models with desuperheater
have 1 desuperheater.
The features of the desuperheater and
the pressure drop curves are given
below.
For Water Temperature °C values,
different from 50°C, multiply the result
obtained by corrective factor.
35
40
45
50
55
60
65
20°C
25°C
45 °C
40 °C
35 °C
30 °C
0
0.5
1
1.5
2
2.5
3
external air temperature d.b.
Temperature of desuperheater produced water ∆t 5° C
Water flow rate l/h
050
070
080 ч 090
100 ч 200
0
0
10
20
30
40
50
60
70
80
90
500
1000
1500
2000
2500
3000
3500
4000
4500
5000
5500
Cd
Average water temperature °C
30
40
50
60
70
Multiplicative coefficients
1.04 1.02
1
0.98 0.96
TAB.14.1.2
050
070
080
090
100
150
200
Heating capacity available
kW
5.4
6.6
8.2
8.9
13.8
17.1
18.9
Water flow rate
l/h
930
1140
1410
1530
2370
2940
3260
Pressure drop
kPa
8
10
11
13
14
24
30
Nominal value refers to:
air temperature
35 °C
water at desuperheater 45/50 °C
∆t
5°C