EcoChill
Chiller
Technical Manual 7300221 V1.1.0_02/2013
External air
temperature (C°)
D.B.
Water Temperature °C
35
40
45
50
Ph
Pe
Ph
Pe
Ph
Pe
Ph
Pe
-10
3.8
1.63
-
-
-
-
-
-
-8
4.0
1.63
3.9
1.76
-
-
-
-
-6
4.2
1.62
4.1
1.76
4.0
1.90
-
-
-4
4.4
1.63
4.3
1.76
4.2
1.90
4.1
2.13
-2
4.6
1.63
4.5
1.76
4.4
1.90
4.2
2.13
0
4.8
1.63
4.7
1.77
4.6
1.90
4.4
2.13
2
5.0
1.63
4.9
1.77
4.8
1.90
4.7
2.13
4
6.0
1.63
5.9
1.77
5.7
1.91
5.6
2.14
6
6.3
1.63
6.2
1.77
6.1
1.91
5.9
2.14
7
6.5
1.64
6.3
1.77
6.2
1.91
6.0
2.14
8
6.6
1.64
6.5
1.77
6.3
1.91
6.2
2.14
10
6.9
1.64
6.7
1.78
6.6
1.91
6.4
2.14
12
7.2
1.64
7.0
1.78
6.8
1.92
6.6
2.14
14
7.5
1.64
7.2
1.78
7.0
1.92
6.8
2.15
16
7.7
1.64
7.5
1.78
7.3
1.92
7.0
2.15
18
8.0
1.64
7.8
1.78
7.5
1.92
7.2
2.15
20
8.3
1.64
8.1
1.78
7.8
1.92
7.5
2.15
External air
temperature (C°)
D.B.
Water Temperature °C
35
40
45
50
Ph
Pe
Ph
Pe
Ph
Pe
Ph
Pe
-10
4.3
1.80
-
-
-
-
-
-
-8
4.6
1.80
4.4
1.96
-
-
-
-
-6
4.8
1.80
4.7
1.96
4.5
2.11
-
-
-4
5.0
1.80
4.9
1.96
4.7
2.11
4.6
2.36
-2
5.2
1.81
5.1
1.96
4.9
2.11
4.8
2.36
0
5.4
1.81
5.3
1.96
5.1
2.11
5.0
2.37
2
5.7
1.81
5.5
1.96
5.4
2.11
5.3
2.37
4
6.7
1.81
6.6
1.96
6.5
2.12
6.3
2.37
6
7.1
1.81
7.0
1.97
6.8
2.12
6.7
2.37
7
7.3
1.81
7.2
1.97
7.0
2.12
6.8
2.37
8
7.5
1.82
7.3
1.97
7.1
2.12
7.0
2.38
10
7.8
1.82
7.6
1.97
7.4
2.12
7.2
2.38
12
8.1
1.82
7.9
1.97
7.7
2.13
7.5
2.38
14
8.4
1.82
8.2
1.98
7.9
2.13
7.7
2.38
16
8.7
1.82
8.5
1.98
8.2
2.13
7.9
2.38
18
9.1
1.82
8.8
1.98
8.5
2.13
8.2
2.38
20
9.4
1.83
9.1
1.98
8.8
2.13
8.4
2.38
IN COOLING MODE
- Water inlet temperature
12 °C
- Water outlet temperature
7 °C
- External air temperature
35 °C
- ∆t
5°C
IN HEATING MODE
- Water inlet temperature
40 °C
- Water outlet temperature
45 °C
- External air temperature
b.s. 7 °C
- ∆t
5°C
Ph Heating capacity (kW)
Pe Input power (kW)
8.
PERFORMANCE IN HEATING MODE MODE
8.1.
ECL 020 H
8.2.
ECL 025 H