10. EVAPORATOR
PRESSURE DROPS
AND USEFUL STATIC
PRESSURES
The standard ECLs (without storage
tank and/or pump are supplied with
installed water filters as per standard:
- for ECL 020 - 025 - 030 - 040 filter
is 1"
- For ECL 050- 070 - 080 - 090 - 100
- 150 - 200 filter is 1 ¼"
NOTE
The pressure drops and the static
pressures are calculated in cooling
mode with 10°C water.
The table below states the correction
to apply to the pressure drops
on variation of the average water
temperature.
10.1. STATIC PRESSURES USEFUL
TO THE SYSTEM
For the "A, P, N, Q" versions (with
storage tank and/or pump only).
The static pressures stated here
are at net of the pressure drops of
the heat exchangers, filter, storage
tank. Therefore are to be considered
USEFUL TO SYSTEM.
NOTE
The static pressures are
calculated in cooling mode.
WITH PRESENCE OF
GLYCOL for static pressures useful
to system PLEASE CONTACT
COMPANY.
0
0
1000
20
40
60
80
100
120
140
160
180
200
2000 3000
4000 5000
6000 7000 8000
9000 10000 11000 12000
020
025 030
0
40
050
070
090
080-1
00
150
200
10.1.1. Standard versions pressure drops
Water capacity l/h
10.1.2. Filters pressure drops
0
0
5
10
15
20
25
30
35
1
2
3
4
5
6
7
8
9
10
1“
1“ 1/4
1“ 1/2
Water capacity mc/h
Average water temperature °C
5
10
15
20
30
40
50
Multiplicative coefficients
1.02
1
0.985
0.97
0.95
0.93
0.91
Water flow rate l/h
Water flow rate l/h
0
0
50
75
25
100
125
150
175
200
225
1000
2000
3000
4000
5000
6000
7000
8000
9000
10000
020
025 030 040
050
070
080 090
100
150
200
0
0
50
100
150
200
250
2000
4000
6000
8000
10000 12000
070
050
080
090
100
150
200
kPa
kPa
kPa
kPa
10.1.3. Useful static pressures with storage tank
and/or standard pump, (A - P)
10.1.4. Useful static pressures with storage
tank and/or increased Q VERSION
NOTE
The Q version with increased pump is only available for ECL
050 - 070 - 080 - 090 - 100 - 150 – 200 sizes