Troubleshooting, It cooling logicool ™ onrak – Airedale OnRak 3kW 35kW User Manual
Page 55

IT Cooling
LogiCool
™ OnRak
IT Cooling
55
Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013
Troubleshooting
FAULT
POSSIBLE CAUSE
REMEDY/ACTION
Unit will not start
No power
Check power supply to the controller.
Wired incorrectly
Check wire connections in accordance with wiring
diagram on control panel.
Loose wires
Check all wires, connections, terminals etc.
Fan not operating - power
on
Power supply failure
Check power supply at circuit breaker.
Wiring to motor
Check voltage at motor terminals.
Motor / fan assembly jammed
Isolate unit and check free rotation of motor/fan
assembly, if faulty
– replace.
Power disconnected to fans.
Carefully check status of power disconnect socket.
Status indication LED faulty Wired incorrectly
Check that the wiring to the LED has the correct
polarity.
Check that the terminations are correct.
Display faulty
Does not illuminate
Faulty cable- Replace cable.
Faulty display
– Replace display.
Wrong display address
Change address of display (see controls section)
No Cooling
Low water flow through coil
Ensure any chilled water valves are open and not
in bypass.
Ensure that any solenoid valves are open when
there is a demand for cooling.
Water temperature sensor faulty. The sensor has
failed causing the valves on the unit to close.
UPS
The UPS system does not operate
correctly
Please refer to the UPS documentation / fault
codes. Various solutions are available from
changing battery modules to module restart.
Water Leak Detection
Damaged flexible hose
Ensure that the flexible hose is not rubbing on the
coil or sheet metal in the vicinity of the door.
Condensation has formed on coil
Check operating conditions ensuring that the unit
operates with its dew point control feature.