Technical data, Design parameters, Logicool ™ onrak active cabinet exhaust it cooling – Airedale OnRak 3kW 35kW User Manual
Page 12

LogiCool
™ OnRak
Active Cabinet Exhaust
IT Cooling
12
IT Cooling
Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013
Technical Data
IMPORTANT
The following information is for general guidance; refer to the certified drawings provided
for installation.
CAUTION
ALL work MUST be carried out by technically trained competent personnel.
The equipment contains live electrical and moving parts, ISOLATE prior to maintenance
or repair work.
A fused and isolated electrical supply of the appropriate rating should be installed.
As standard the equipment is designed for 230V
10%, 1 Phase, 50Hz to all relevant IEE
regulations, British standards and IEC requirements.
Design Parameters
The OnRak is designed for operation at air on dry bulb temperatures and water approach temperatures as standard:
* Minimum water temperature is always 2°C above the dew point temperature of the air
Approach Water Temperature*
Air On to Coil
(Server Discharge)
60°C
16°C
10°C
46°C
18°C
Normal
working
area
Application
limits
20°C
0.0105 /
(7%RH)
0.0065 /
(57%RH)
moisture
content
kg/kg (dry
air)
Application
limits