Chilled water valve (2+3 way), It cooling logicool ™ onrak – Airedale OnRak 3kW 35kW User Manual
Page 31

IT Cooling
LogiCool
™ OnRak
IT Cooling
31
Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013
Chilled Water Valve
(3 Way)
The chilled water valve has an indication of flow on the stem. The actuator is securely
attached to the top of the valve so that when there is a demand for cooling the valve
opens allowing water to flow through the coil. No demand, the water goes through the
bypass (0 VDC no demand, 10 VDC 100% demand).
(A) Flow to coil
(B) Bypass leg
(C) Common
Valve in full flow to coil (C to A)
Valve in flow to bypass (C to B)
Valve Actuator Orientation
CAUTION
The chilled water valve electrical connection must be a maximum of 3m away from
the customer terminal box. This is to ensure EMC Compatibility.
B
C
A