West Control Solutions KS 800 Profibus Interface Manual User Manual
Page 38
Rem. B2 Cntrl_x: (Code 39)
MSB
LSB
D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
Bit no.
Name
Allocation
Status ‘0’
Status ‘1’
D0
A/M
Automat/Manuel
Auto
Manuel
D1
Coff
Switch the controller off
no
yes
D2
w/w2
w/w2 switch over
w
w2
D3
we/wi
wext/wint
wext
wint
D4
OStart
Start the optimisation
no start
start
D5
Ostop
Stop the optimisation
no stop
stop
D6...D15 "0"
Always "0"
Set-point
Set-point processing (function no.:1)
Code
Descr.
R/W
Type
Description
Range
Rem.
00
Block
R
Block
Block access (1, 3)
01
WState
R
ST1
Set-point status
B
03
Wint
R
FP
Effective internal set-point
30
Block
R
Block
Block access (31...32)
31
Wnvol
R/W
FP
Int. set-point, non-volatile
-999..9999
32
Wvol
R/W
FP
Int. set-point, volatile
-999..9999
Rem. C WState: (code 01)
MSB
LSB
D7
D6
D5
D4
D3
D2
D1
D0
Bit no. Name
Allocation
Status ‘0’
Status ‘1’
D0
w/w2
w/w2 switch-over
w
W2
D1
we/wi
wext/wint
wext
wint
D2
w/wanf
start-up set-point switch-over w
wanf
D3
GRW
Gradient function active
no
yes
D4
Weff_fail Error effective set-point
no
yes
D5
‘0’
always ‘0’
D6
‘1’
always ‘1’
D7
Parity
Output variable
Output variable processing(function no.:4)
Code Descr.
R/W Type
Description
Range
Rem.
30
Block
R
Block Block access (31, 35)
31
dYman R/W FP
Difference output variable
-210..210
32
Yman
R/W FP
Absolute output variable
-105..105
33
Yinc
R/W INT
Increment. output variable
0, 1
34
Ydec
R/W INT
Decrement. output variable
0, 1
35
Ygrw_ls R/W INT
Speed for incr./decr. output variable offset
0, 1
Tuning
Self-tuning(function no.:5)
Code Descr.
R/W Type
Description
Range
Rem.
00
Block
R
Block Block access (1, 3)
1
State_Tune1
R
ST1
Status Tuning
D
3
ParNeff
R
INT
Eff. parameter set number
0...1
30
Block
R
Block Block access (31...39)
31
ParNr
R/W INT
Parameter set number effective
0 .. 1
32
Tu1
R
FP
Delay time heating
0...9999 s
33
Vmax1
R
FP
Rate of increase heating
0,000...9,999 %/s
34
Kp1
R
FP
Process gain heating
0,000...9,999
35
MSG1
R
INT
Error code of self-tuning heating
0...8
36
Tu2
R
FP
Delay time cooling
0...9999 s
37
Vmax2
R
FP
Rate of increase cooling
0,000...9,999 %/s
38
Kp2
R
FP
Process gain cooling
0,000...9,999
39
MSG2
R
INT
Error code of self-tuning cooling
0...8
Function block protocol
9499 040 50511