3.5.4
Data read procedure
Start telegram:
Master sends: Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
0x10
ID1
Code
FB no. Fct._no. Type
0
0
Controller
replies:
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
0x10
Numb. real values
1)
Numb. integer values
1)
Data telegrams:
Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2 Byte 3
Byte 4 - 7
0x68 count
0x68 count
Value
Thereby, the first value is sent with Count = 1. For flow control, count is reflected by KS800 (? once). The
values are transmitted in the order real - integer.
End telegram:
Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2-3
Byte 4 - 7
0x16
0x16
Result
3.6
Examples
3.6.1
Function block protocol principles
A function block has input and output data (process data) as well as parameter and configuration data. It is
addressable via a function block number.
The following access mechanisms are used:
3.6.2
Individual access
This access (code xx) can be used for reading or writing an individual value of a function.
Valid values for ID1:
Configuration as
FixPoint:
0 = integer
real values are transmitted as integer (without digits behind the decimal point)
1 = real
real values are transmitted as FixPoint (1 digit behind the decimal point)
Example 1:
(message structure with data sending)
Transmission of parameter set number (ParNr = 1) to the controller (channel 2).
Start telegram:
Master sends: Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
0x10
0
31
52
5
0
0
1
Controller
replies:
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
0x10
Data telegrams:
Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1 Byte 2 Byte 3
Byte 4 - 7
0x68
1
1
0x68
1
End telegram:
Master sends: Byte 0 Byte 1 Byte 2 Byte 3 Byte 4 - 7 Controller replies: Byte 0 Byte 1
Byte 2 - 3
Byte 4 - 7
0x16
0x16
0
Process data
9499 040 50511
18