West Control Solutions KS 800 Profibus Interface Manual User Manual
Page 36
![background image](/manuals/370866/36/background.png)
5.2.5
INPUT (FB no.: 60 ... 67 Type no.: 112)
All data which concern acquisition and processing of all input values (analog/digital) are grouped in function
block ‘INPUT’. The data are available once per controller channel.
Process data
General
input processing of analog signals
(function no.: 0)
Code Descr.
R/W Type
Description
Range Rem.
00
Block
R
Block
Block access (1, 3)
1
Input_x_Fail
R
ST1
Signal input x fail
A
3
x1
R
FP
Main variable
10
Block
R
Block
Block access (13, 18)
13
INP1
R
FP
Raw measurement value before measured value correction
18
Function Type
R
INT
Type no. of function block
112
Rem. A Status byte Input_X_Fail:
MSB
LSB
D7
D6
D5
D4
D3
D2
D1
D0
Bit no.
Name
Allocation
Status ‘0’
Status ‘1’
D0
INP1F
Input 1 fail
no
yes
D1...D5 ‘0’
always ‘0’
D6
‘1’
always ‘1’
D7
Parity
Parameter a. configuration data
ME/V1
Measured value INP1 : acquisition and processing
(function no.: 1)
Code
Descr. R/W
Type Description
Range
Rem.
B2
41 X1
in
R/W
FP
Measured value correction X1 input
-999..9999
42 X1
out
R/W
FP
Measured value correction X1 output
-999..9999
43 X2
in
R/W
FP
Measured value correction X2 input
-999..9999
44 X2
out
R/W
FP
Measured value correction X2 output
-999..9999
B3
71 X0
R/W
FP
Phys. value at 0%
-999..9999
72 X100
R/W
FP
Phys. value at 100%
-999..9999
73 X
Fail
R/W
FP
Substitute value with sensor fail
-999..9999
74 T
fm
R/W
FP
Filter time const. measured value process.
0.0 .. 999.9
75 T
kref
R/W
FP
Reference TC
0...60 °C / 32...140°F
76 C200
R/W
INT Type: sensor type
Unit: unit
(T,H)
(Z)
0..xxy0
77 C205
R/W
INT Fail:
sensor break behaviour
STk:
Source Tk
XKorr: enable process value corr.
(T)
(H)
(Z)
1..wxy0
78 C190
R/W
INT Signal allocation of digital signals:
Controller off
w/w2
(Z)
(E)
0...00xy
Function block protocol
9499 040 50511
36
990914