Flow - outputs menu - alarm relay 7.17 – Metex Shark Multi-Parameter Controllers & Analyzers User Manual
Page 128
![background image](/manuals/369863/128/background.png)
S
H
A
R
K
MULTI-PARAMETER CONTROLLER & ANALYZER USER’S MANUAL
Flow - Outputs Menu - Alarm Relay 7.17
Flow - Outputs Menu - Alarm Relay 7.17
Page 126
DOWN
DOWN
DOWN
DOWN
DOWN
UP
DOWN
DOWN
UP
DOWN
With "N" selected, pressing the
key will NOT store the selection, but
simply return to the OUTPUTS Menu.
This function is useful if you wish to
view the current selection without
making any changes.
DOWN
TO OUTPUTS MENU
Not stored
DOWN
Then press the key to store the
selection and return to the OUTPUTS menu
Stored
the Y character.
Or press the key to highlight
The FAIL SAFE feature is designed to reverse the
normal action of the relay.
When set to FAIL SAFE OFF, the relay will operate
as a normal relay, which means that when the
relay is not energized the NO contacts are open,
and a device connected via the NO contacts is
turned off. When the relay becomes energized the
device turns on.
When the relay is set to FAIL SAFE ON, the
normal action of the relay is reversed. Thus the NO
contact acts as the NC contacts and the NC acts
as the NO. Therefore the device connected to the
NC contacts will be turned on when the relay on
set-point is reached. Actually the relay will be de-
energized but because it is acting in reverse the
device will be turned on. When the relay off set-
point is reached the relay will energize and the
device connected to the NC contact will turn off.
The reason that the Fail Safe option would be used
is to have the device turned on in the event of a
power interruption.
The HIGH OFF set- point is the value that the
must reach in order to de-energize the alarm relay
after it has increased over and tripped the HIGH
ON set-point. This value must be lower than the
HIGH ON Set-point.
FROM HIGH ON
UP
NOTE
PRESS THE AND KEYS
TOGETHER TO GO IMMEDIATELY BACK TO
RUN MODE
DOWN
If you wish to change the setting,
press the key once which
will move the cursor to the first
character of the value to be changed
Press the key once
which will move the cursor
back to the RH side of the
display.
UP
Use the and
keys to change the setting
DOWN
If you wish to change the setting,
press the key once which
will move the cursor to the first
character of the value to be changed
If you wish to change the setting,
press the key once which
will move the cursor to the first
character of the value to be changed
Press the key once
which will move the cursor
back to the RH side of the
display.
DOWN
Press the key to accept the
setting and move to the next setting
UP
Use the and
keys to change the setting
DOWN
If the Low On set-point is set higher than the factory
default Low Off set-point, when the user advances
from the low on set-point to the Low Off set-point the
controller will adjust the Low Off set-point to be equal to
the Low On set-point. If the user then tries to decrease
the Low Off set-point the Controller will display the Low
Alarm setup error screen.
This screen will be displayed for 10 seconds, then return
back to the setup screen that was previously displayed.
The same conditions apply to the High alarm set-points.
Except the High Off set-point must be lower than the High
On set-point. If the user tries to increase the High Off set-
point higher than the High On set-point the High Alarm
setup error screen will be displayed.
If the user sets the low on set-point and the low off set-
point equal to 0, it will disable the Low Alarm relay.
Similarly, setting the High On set-point and the HIGH
OFF set-point to 0 will disable the High Alarm.
ON SPT < OFF SPT
LOW ALARM
ON SPT > OFF SPT
HIGH ALARM
STORE? Y N
STORE? Y N
ALARM RELAY
ALARM RELAY
FAIL SAFE ON >
FAIL SAFE O N >
FAIL SAFE O FF >
HIGH OFF 88.00 >
HIGH OFF 88.0 0 >
HIGH OFF 70.0 0 >
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
ALARM RELAY
FAIL SAFE OFF >
ALARM RELAY
ALARM RELAY
HIGH OFF 70.00 >