8.3 Preparation for measurement
Before testing, always check the following:-
1 The ‘low battery’ Indication is not displayed
2 There is no visually obvious damage to the tester or to the test leads
3 Test the continuity of the test leads by switching to continuity test and shorting out
the lead ends. A high reading will indicate that there is a faulty lead or that the fuse is
blown.
4
Make sure the circuit to be tested is not live. “Live Circuit” warning is displayed if
the instrument is connected to a live circuit but test the circuit as well!
Operation of Function Switch
F1 N/A
F2 N/A
F3 N/A
F4 Voltage setting
8.4 Insulation resistance measurement
The KEW6016 has three selectable test voltages of 250V, 500V and 1000V DC.
1 Select INSULATION function with the Rotary switch.
2. Press the VOLT Switch (F4) and select desirable voltage range.
3. Insert the Test Leads to the L and PE terminal on KEW6016 respectively as shown in
Fig.19.
L terminal
Red cord of Model7188, or
Model7196 Remote Test Lead
PE terminal
Green cord of Model7188
Fig.18
Fig.19