8.4 CONNECTING CABLES

NOTE:
The below described cables are shown in the connection diagram on the following page.



Cable A:
Quad coaxial cable
Type MR04 (to be supplied by Krohne Altometer)

Technical data:

Test voltage

≥ 500 V

Diameter of strand (core and screen)

≥ 0.1 mm

Distributed capacitance (core/screen)

67 pF/m

Distributed inductance (core/screen) 0.4

µH/m



Cable B:
Power supply cable
Cable parameters must be in accordance with the regulations in the EN 60079-14 "Electrical installations in
hazardous locations" or an equivalent national standard (e.g. DIN VDE 0165).

Rated voltage

≥ 500 V


Examples: H07..-.,

H05..-.



Cable C:
Signal cable for current output and binary outputs (pulse and status output).
Cable parameters must be in accordance with the regulations in the EN 60079-14 "Electrical installations in
hazardous locations" or an equivalent national standard (e.g. DIN VDE 0165).


Bonding conductor:
Minimum cross-sectional area

4 mm

2

(AWG 10)