KROHNE GFM 700 EN User Manual
Page 15
15
Fct. Text
Description
and settings
3.3.0
CUR.OUTP. I Submenu 3.3.0 Current output I
3.3.1 FUNCTION
I
Function, current output I
• OFF (switched off)
• F/R IND.
(F/R indication, e.g. for F)
• 1 DIR. (1 flow direction)
• I
(Forward / Reverse flow,
e.g. in 0 - 20 mA range:
F=10 - 20 mA and R=10 - 0 mA)
• 2 DIR. (Forward/Reverse flow,
F/R-measurement)
• SP. SOUND (sound velocity)
3.3.2
RANGE I
Range for current output I, see
Sect. 5.7.2
• 0 - 20 mA
• 4 - 20 mA
• OTHER RANGE
(see Fct. 3.3.3, 3.3.4 + 3.3.5)
3.3.3
I 0 PCT.
Current for 0% flow (I
0%
)
(appears only if OTHER RANGE
set under Fct. 3.3.2).
Value: 00 to 16 mA
3.3.4
I 100 PCT.
Current for 100% flow (I
100%
)
of full-scale range (Fct. 3.1.1)
(appears only if OTHER RANGE
set under Fct. 3.3.2).
Value: 04 - 20 mA
(value must be at least 4 mA
greater than that of Fct. 3.3.4).
3.3.5
I MAX mA
Current limitation (I
max
)
see Fct. 5.7.2
(appears only if OTHER RANGE is
set under Fct. 3.3.2)
Value: 04 20 mA
(value must be at least 4 mA
greater than that of Fct. 3.3.4).
3.3.6 TIMECONST.
I
Time constant of current output I
Value: 0.04 - 3600 Sec
3.3.7 L.F.CUTOFF
I
Low flow cutoff (SMU) for current
output required?
Setting: NO or YES
3.3.8 L.F.CUTOFF
ON
Cutoff “on” value for SMU-I
(appears only if YES set
under Fct. 3.3.7)
Value: 01 - 19 PERCENT of Q
100%
(Fct. 3.1.1)
3.3.9 L.F.CUTOFF
OFF
Cutoff “off” value for SMU-I
(appears only if YES set
under Fct. 3.3.7)
Value: 02 - 20 PERCENT of Q
100%
(Fct. 3.1.1), value must be greater
than that of Fct. 3.3.8.