beautypg.com

4 table of settable functions – KROHNE IFC 110 Converter EN User Manual

Page 28

background image

28

IFC 110 F

05/2003

4.4

Table of settable functions


Abbreviations used:

A1, A2 Status outputs

P (P2) Pulse output (2nd pulse output A1)

(A1 can also be 2nd pulse output A1)

P

max

= F

max

/Q

100%

C1, C2 Control inputs

P

min

= F

min

/Q

100%

D1, D2 Status outputs

Q

Current flow rate

DN

Meter size, nominal size

Q

100%

100% flow rate = full-scale range

F

max

= ½ x pulse width (s) for

≤ 50 Hz

≤ 10 kHz if ”AUTO” or ”SYM.” are selected in Q

max

= /4 DN² x v

max

(= max. full-scale range

subfunction ”PULSWIDTH”

Q

100%

at v

max

= 12 m/s or 40 ft/s)

F

min

= 10 pulses/h

F

M

Conversion factor volume for any unit,

Q

min

= /4 DN² x v

min

(= min. full-scale range

see Fct. 3.05 ”FACT. VOL.”

Q

100%

at v

min

= 0.3 m/s or 1 ft/s)

F

T

Conversion factor time for any unit,

SMU

Low-flow cutoff for I and P

see Fct. 3.05 ”FACT. TIME”

v

Flow velocity

GK

Flow sensor constant

v

max

Maximum flow velocity (12 m/s or 40 ft/s) at Q

100%

I

Current output

v

min

Minimum flow velocity (0.3 m/s or 1 ft/s) at Q

100%

I

0%

Current at 0% flow rate

F/R

Forward/reverse flow in F/R measuring mode

I

100%

Current at 100% flow rate


Fct. Text

Description

and

setting

1.0

OPERATION

Operating menu

FULL SCALE

Full-scale range for flow rate Q

100%

Selection of unit

• m³/h

• Liter/Sec

• US.Gal/min

• user unit, factory setting ”Liter/h” or ”US MGal/day” (see Fct. 3.05)

Press

key to change to numerical setting

Setting

ranges

The range depends on the nominal width (DN) and the

flow velocity (v):

Q

min

= DN² x v

min

Q

max

= DN² x v

max

Nominal width/meter size

v

min

= 0.3 m/s (1 ft/s)

v

max

= 12 m/s (40 ft/s)

● DN 2.5–1200 /

1

/

10

”–48”:

0.0053

– 48 860 m³/h

0.0237

– 218 560 US.Gal/min

● DN 1300–3000 / 52”–120” 1435

– 305 360 m³/h

(see Section 8.6)

6415

– 1 366 000 US.Gal/min

Press

key to return to Fct. 1.01 FULL SCALE

VALUE P

Pulse value for pulse output P (Fct. 1.06 ”VALUE P”) and/or

and/or

for the 2nd pulse output A1 (Fct. 1.07 ”VALUE P2”) has been changed.

VALUE P2

With the ”old” pulse values the output frequency (F) would have

been exceeded or would not have been reached.

P

min

= F

min

/ Q

100%

P

max

= F

max

/ Q

100%

Check new values!

1.02 TIMECONST. Time

constant

Selection: ● ALL (applies to display and all outputs)

● ONLY I (only display, current and status outputs)

Press

key to change to numerical setting.

Range:

● 0.2 – 99.9 Sec

Press

key to return to Fct. 1.02 TIMECONST.

1.03

L.F. CUTOFF

Low-flow cutoff (L.F. CUTOFF)

● OFF (fixed tripping points: ON = 0.1% / OFF = 0.2%)

● PERCENT (variable tripping points)

ON

OFF

1 – 19%

2 – 20%

Press

key to change to numerical setting.

Note: the cutoff ”OFF” value must be greater than the cutoff ”ON” value.

Press

key to return to Fct. 1.03 L.F. CUTOFF.

π

4

π

4

π

4

π

4