7.3

Technical data: limit switches


Limit switch

MS 20/STD

MS 20/EXI

Max. switching capacity

30 VA

0.5 A

0.5 A, 230 V AC

Ambient temperature

–20°C … 120°C
–4°F … 250°F

-20°C … +80°C
-4°F … 175°F (T6) or
-20°C … +95°C
-4°F … 200°F (T5)

Process temperature

< 250°C / < 480°F

< 250°C / < 480°F

Protection category

IP 65

IP 65

to EN 60529

NEMA 4/4X

NEMA 4/4X

Cable entry

PG 9

PG 9

Max. safety values

- Ui=

****

Ii = 100 mA
Ci= 0 nF, Li= 0 µH

Housing material

polycarbonate polycarbonate

Hysteresis

0

0

Weight

85 g / 0.2 lb

85 g / 0.2 lb


Limit switch

MS 15/STD

MS 15/EXI MS

15/EXD

MS15/*/NAMUR

max. switching capacity

20 VA

1.5 A

According to

LC (low power cut-out)

1.5 A, 250 V AC

20 VA
1.5 A
250 V CA*****

NAMUR 19234

max. switching capacity
HC (high power cut-out)

Max. 100 VA
Min. 3VA
1.5 A
250 VA

-

Min. 3 VA
1.5 A
250 V CA*****

*

Ambient temperature

–20°C … 120°C ***

***

*

–4°F … 250°F

Process temperature HT
(high)

< 250°C
< 480°F

*** *** *

Process temperature BT
(low)

< 300°C
< 570°F

*** *** *

Protection category

IP 65

IP 65

IP 65

*

to EN 60529

NEMA 4/4X

NEMA 4/4X

NEMA 4/4X

Cable entry PC
AL

PG 13.5
M 20 x 1.5**

PG 13.5
M 20 x 1.5**

-
M 20 x 1.5**

*

Max. safety values

- Ui=****

Ii =500 mA
Ci=0nF,Li= 0µH

*****

*. For Exi :
Ui=24V, Ii = ****,
Ci=0nF, Li= 0µF

Housing material BT
HT

Polycarbonate
Aluminium

Polycarbonate
Aluminium


Aluminium

*

Hysteresis

0 0 0

*

Weight PC
AL

130 g / 0.3 lb
1200 g / 2.6 lb

130 g / 0.3 lb
1200 g / 2.6 lb

-
1200 g / 2.6 lb

*

*

For these characteristics refer to the other columns in the table above for STD (i.e. non-Ex),
EXI or EXD switches – depending on which official approval has been selected.

**

standard thread (fitting not supplied). Optional: M25 x 1.5 or NPT ¾.

***

Refer to table in “ATEX applications: special conditions for safe use”, section 7.1

****

The value is not defined, however the power supply must be intrinsically-safe

***** U

max

= 380 V CA, I