Installation and Operating Instructions BM 26 A

1.6.4 Correcting the scale position to accurately read true liquid level

The scale* can be corrected by the customer using the following procedure:
Step Action
1

Find the float immersion depth “c” (supplied by KROHNE, refer also to section 1.6.3).

2

Subtract the dimension “a”, float base to magnet centreline (given on the float dimensioned
drawing in Section 1.6.2), from “c” to get the dimension “b”, scale correction factor.

Item Description

b =

c – a (difference between liquid level
and indicator position due to product
density)

c =

float immersion depth (a function of
product density), see section 1.6.3.

a =

distance from centerline of magnet
system to the float base, see
dimensioned float drawings in
section 1.6.2.

1

=

Float

2 =

Follower magnet of indicator (or limit
switch)

3 =

Position of magnets mounted in the
float

3

Loosen the two clamp collars holding the measuring scale onto the measuring tube using a
screwdriver or 8 mm wrench.

4

Bring the zero point (top of the lower red KROHNE plate) on the scale into line with the
centreline of the bottom lateral process connection.

4a

Undo top collar

1 Measuring

scale

2 Measuring

tube

3

Top measuring scale collar

*This information also applies to the initial setting up of limit switches – however, the fitter should
also remember to take into account the limit switches offset trigger point (see section 3.6).