It is assumed in this section that flowmeter has already been
installed. (for installation details refer Sect. 2+3)
Following are some trouble shooting hints.

SYMPTOMS: Display is blank.
· DC Supply voltage (between term. 5/6) is not

available (voltage range 12-36 Vd.c).

· Supply connected with reverse polarity

Important: Ensure that the screw threads of the covers on
the electronics and connection compartments are well
greased at all times

· Electronics faulty

SYMPTOM: Current output is not proper.
· Check current output electronics (refer Sect.7.2.3)

· Check that current output loop resistance is less

than Rmax specified by Section 3.3.2

SYMPTOM: Pulse output is incorrect
· Check the Pulse output electronics (refer Sect.7.2.4)

· Check programming of pulse output. (Functions

Fct1.3.x )
· Check that pulse output is not overloaded. For load

ratings of pulse output refer Sect.3.3.3.

SYMPTOM: Non zero flow indicated when no
actual flow in the pipe.

· Mains

interference

due

to

improper

earthing.

The

protective

earth

PE

terminal

should

be

properly grounded.

· Excessive mechanical vibration in the pipe.

If so, support the pipeline near the flowmeter

perpendicular to both the axis of pipe and the axis

of bluff body.

SYMPTOM: Flowrate indicated is 0.0 even with flow in
the pipe.

· Vortex sensor cable disconnected or not properly

connected.

· Flow sensor faulty – some checks are given in

Sect.7.1.1

· Electronics faulty (preamplifier)

· Fct. 3.3.4 Gain too low: Set gain to value of 5 or greater &

check.

SYMPTOM: Fatal error INV. CONFIG (invalid
configuration)

· Configuration data in the non-volatile memory is

inadvertently corrupted. Go to the programming
mode and recheck (reprogram, if necessary) all
the settings. If error persists contact Forbes Marshall service.

SYMPTOM: Display contrast is progressively Fading.
· Never expose display directly to the sunlight!

Install a sunshade if necessary.


SYMPTOM: Flow indicated responds to changes in flow
but indicated value does not correspond to actual flow
rate.

8. Trouble shooting hints

· Check programming of Fct.3.1.2 K-Factor which should be

same as on the nameplate.

· Meter not properly centered on the pipeline. The axis of

meter bore should be aligned with that of pipe.

· Gaskets at the meter are protruding into pipe bore.

Gaskets must not project into effective cross-
section of the pipe.

· Irregularities on the surface of the pipe bore.

The pipe bore should be free from irregularities
at the welded joints, dirt, deposits and excessive
surface roughness.

· Vortex signal is falsified due to a bi-phase medium.

Bi-phase media are not permitted. Use a moisture
separator for wet steam applications to remove
moisture droplets from the steam. Use suitable
filters

in

gas

applications

to

remove

solid

particles from the flowing gas.

· Incorrect

angular

position

of

the

meter

Refer to Sect.2.1 (1) for allowable mounting positions.

· Insufficient upstream / downstream pipe lengths.

Check that upstream / downstream pipe lengths are of
correct minimum length as given in Sect.2. 1(3).

· Check the flow direction & direction of arrow on

the primary!