OPERATION

5

29

OPTITEMP TT 30 C/R

www.krohne.com

11/2012 - 4000753302 - MA OPTITEMP TT 30 C/R R02 en

• Plug the connector into the interface of the PC.

i

The cable connection has been established, you can start the PC configuration of the
transmitter now.

• After configuration plug the cover into the female connector again to prevent the connector

from dirt.

5.2 Factory settings for configuration

The transmitters are delivered either with the following factory settings or configured according
to customers' specifications:

INFORMATION!
After a successful PC configuration the transmitter is ready for operation, a calibration is not
required.

Transmitter

Input

Output

Sensor break

In-head version (Non-

Ex)

Pt100, 3-

wire connection,

0...+600°C /

+32...+1112°F

4...20 mA

On

In-head version (Ex)

Pt100, 4-

wire connection,

0...+100°C / +32...+212°F

Rail-mount version

(Non-Ex)

Pt100, 3-

wire connection,

0...+600°C /

+32...+1112°F

Rail-mount version (Ex)