Technical data – KROHNE OPTITEMP TT 10 C-R EN User Manual
Page 44
7
TECHNICAL DATA
44
OPTITEMP TT 10 C/R
www.krohne.com
02/2013 - 4000752703 - MA OPTITEMP TT 10 C/R R03 en
Installation conditions
Mounting
In-head transmitter: "B connection head" or larger according to DIN 43729;
with the help of the rail mounting kit you can also fix this transmitters on a
DIN rail according to EN 60715 TH35 (formerly EN 50022) ( refer to
Rail
mounting kit for in-head transmitters on page 18).
Rail-mount transmitter: rail according to EN 60715 TH35 (formerly EN
50022), 35 mm / 1.38".
For detailed information refer to chapter "Installation".
Weight
In-head transmitter (Non-Ex and Ex version): 40 g / 0.09 lb
Rail-mount transmitter: 55 g / 0.12 lb
Dimensions
For detailed information refer to
Dimensions on page 45.
Materials
Housing
In-head transmitter: PC (Non-Ex), Zinc alloy + PC (Ex version)
Rail-mount transmitter: PC + Glassfibre
Flammability acc. to UL
V0 (all versions)
Electrical connections
Power supply
Power supply
Power supply
Power supply
In-head transmitter: 6.5...32 VDC (Non-Ex version), 8.5...30 VDC (Ex version)
Rail-mount transmitter: 6.5...32 VDC
Galvanic isolation
No
Connection
Single/stranded wires: max. 1.5 mm
2
/ AWG 16
Polarity protection
Standard for all versions
Inputs / Outputs
Input
Input
Input
Input
Pt100 (IEC 60751, α=0.00385)
Type of connection: 3-wire
Span: 50/100/150/200/300/400/500°C and 100/200/300/400/600/800/1000°F
Zero point: -50...+50°C / -60...+120°F
Fine adjustment of span: ±10% of span (±5% for 600, 800 and 1000°F)
Thermocouple
Configuration span: 9 mV to 55 mV continuous
Corresponding to:
T/C J: 170-950 °C / 305-1710 °F
T/C L: 165-900 °C / 300-1620 °F
T/C K: 220-1370 °C / 400-2470 °F
T/C N: 290-1300 °C / 520-2340 °F
T/C T: 200-400 °C / 360-720 °F
Zero point: ±10% of span
Output
Output
Output
Output
Output signal
4...20 mA, temperature linear, 2-wire connection
4...20 mA, mV linear, 2-wire connection
Update time
≤ 200 ms
Permissible load
In-head (Non-Ex) and rail-mount transmitter: 700 Ω at 24 VDC and 25 mA
In-head transmitter (Ex): 620 Ω at 24 VDC and 25 mA
NAMUR compliance
NAMUR NE 21 (for frequencies ≥ 150 kHz)
.book Page 44 Tuesday, February 26, 2013 1:43 PM