beautypg.com

Figure 3. master power up screen – KEPCO KIT 219-0445, Cables for two High Power BOPs User Manual

Page 4

background image

KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11352 U.S.A. " TEL (718) 461-7000

FAX (718) 767-1102 " email: [email protected]

4

228-1472 REV 3

091903

3.

Turn on the unit to be configured as a master and note that upon power up the FAULT light will go

on (this is normal). Proceed as follows:

a.

From the main screen, press

%

to enter the Settings Menu.

b.

From the Settings menu, gain access to the Protected Settings menu by first entering the

password (see Step 2c above).

c.

From the Protected Settings menu, highlight

Unit Type

(use ADJUST control or

Y

or

U

keys) and press

!

to modify. Highlight

Master +1

and press

!

to apply the change.

d.

From the Protected Settings menu, under

Unit Type

highlight

Expansion

and press

!

to

modify. Highlight

Parallel

and press

!

to apply the change.

e.

Exit the Protected Settings menu by pressing

$

to test the system and to save the settings

for subsequent power-up cycles. The display shows the master power-up screen (see Fig-

ure 3).

NOTE: Pressing

%

to exit will cause the unit to revert to a standalone unit.

f.

The power-up master module screen (Figure 3) changes to show the status of Slave 1 (see

Table 2).

If the slave is recognized as ready, after about 10 seconds the master LCD reverts to the

Power On Default screen (see Figure 4). The slave also displays the Power On Default

screen (see Figure 5), except the unit will be in Current Mode, no function keys are active

and the Status message at the bottom is

KPAD Locked

, indicating the keypad is disabled.

The fault indicators on both units are off.

If the master power-up screen is still displayed after 10 seconds, the slave was not properly

recognized. Pressing

%

or turning power off, then on again, reconfigures the unit as a stan-

dalone unit. Verify that the BITBUS cable is installed correctly. Verify that the slave has

been properly configured as a slave per step 2 above. Repeat step 3. If the power up

screen still does not revert to the power on default screen, refer to troubleshooting.

FIGURE 3. MASTER POWER UP SCREEN

VOLTAGE

SOURCE

CPROTECT

VOLTAGE

CURRENT