EQUITEST

5071

EN - 33

In "

" mode, if one of

the Phase-Phase
voltages does not reach
the minimum threshold
value of 100V, the
instrument does not
perform any test and
displays the following
screen.

Check that all phases of
the electric system
being tested have
voltage.

30.11.12


- - -


FRQ =50.0HZ V1-2=391V
V2-3= 0 V V3-1= 0V

 LOW VOLTAGE L3

PHASE ROTATION

Phase "L3" does not reach
the minimum voltage value

FUNC

Using the "

" mode, if

two phases of the
electric system coincide,
the instrument does not
perform any test and
displays the following
screen.

Check that all phases of
the electric system
being tested have
voltage.

30.11.12


- - -


FRQ =50.0HZ V1-2=407V
V2-3= 0 V V3-1=407V

 PHASE DOUBLED

PHASE ROTATION

Two phases of the three-
phase system being tested
are connected to each
other

FUNC

Using mode "

", if

phase sequence is
incorrect, the symbol
"132" is displayed.
Exchange two phases of
the electric system being
tested and repeat the
test.

30.11.12

This symbol DOES NOT
indicate that input B1 is
connected to phase L1,
input B2 is connected to
phase L3, input B3 is
connected to Phase L2. It
ONLY indicates that the
detected phase sequence
is incorrect


132


FRQ=50.0HZ VR-S= 391V
VS-T= 392V VT-R= 398V

 INCORRECT

PHASE ROTATION

Incorrect sequence

FUNC