beautypg.com

HT instruments EQUITEST5071 User Manual

Page 28

background image

EQUITEST

5071

EN - 26

At the end of the test,
the instrument gives out
a double sound to
indicate that test has
been correctly
performed and the
following screen
appears on the display.

LOOP

30.11.12

Value of Phase-Earth
impedance expressed in

.


1.07

215A



Freq=50.0HZ
VP-N=231V Vp-PE=231V



P-PE

Value of the assumed Phase-
Phase short-circuit current
calculated using the formula
reported below

FUNC Z2

Operating mode


N.B.: In TT systems, the value of impedance measured by the instrument may only be

attributed to the value of overall earth resistance. Therefore, in compliance with
standard CEI 64-8, the measured value may be taken as the value of the system’s
earth resistance.

Formula used for calculating the assumed short-circuit current:

PE

N

CC

Z

U

I

where: U

N

= Phase-Earth voltage 127 if

100< V

mis

 150

230 if 150V< V

mis

260

Z

PE

= measured Phase-Earth impedance


6. The results can be saved by pressing the SAVE key twice (see § 7.1).