beautypg.com

Caution – HT instruments EQUITEST5071 User Manual

Page 25

background image

EQUITEST

5071

EN - 23

CAUTION

The following test entails the circulation of a maximum current of approx. 6A
between phase and neutral. This could cause the tripping of possible
magnetothermal protections with lower tripping currents. In this case, carry
out the measurement upstreams of the protections.


CAUTION

When message "MEASURING…" is displayed, this indicates that the
instrument is carrying out the test. Never disconnect the instrument’s leads
during this phase.

At the end of the test,
the instrument gives out
a double sound to
indicate that test has
been correctly
performed and the
following screen
appears on the display.

Value of Phase-Neutral Line
impedance expressed in
Ohm

LOOP

30.11.12


1.07

215A



FRQ=50.0HZ
VP-N=231V VP-PE=231V


P-N

Value of the assumed Phase-
Neutral short-circuit current
calculated using the formula
reported below

FUNC Z2

Formula used for calculating the assumed short-circuit current:

PN

N

CC

Z

U

I


where U

N

= Phase-Neutral voltage

127 if V

mis

 150

230 if 150V< V

mis

260

Z

PN

= measured Phase-Neutral impedance



6. The results can be saved by pressing the SAVE key twice (see § 7.1).