beautypg.com

HT instruments EQUITEST5071 User Manual

Page 30

background image

EQUITEST

5071

EN - 28

At the end of the test,
the instrument gives out
a double sound to
indicate that test has
been correctly
performed and the
following screen
appears on the display.

LOOP

30.11.12

Value of Phase-Earth
resistance expressed in


1.07

215A



Freq=50.0HZ
VP-N=231V Vp-PE=231V


R

A

Value of the assumed Phase-
Earth short-circuit current
calculated using the formula
reported below

Operating mode

FUNC

N.B. In TT systems, the value of overall earth resistance may be considered similar to

the value of Phase-Earth fault loop impedance, measured by the instrument.
Therefore, in compliance with standards, the measured value may be taken as the
value of the system’s earth resistance.

Formula used for calculating the assumed short-circuit current:

PE

N

CC

Z

U

I

where: U

N

= Phase-Earth voltage 127 if

100< V

mis

 150

230 if 150V< V

mis

260

Z

PE

= measured Phase-Earth impedance


6. The results can be saved by pressing the SAVE key twice (see § 7.1).