Programming Reference Sheets
52
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Appendix C
Programming Reference Sheets
❐
00
❐
01
❐
02
❐
03
❐
04
❐
05
❐
06
❐
07
❐
08
❐
09
❐
10
❐
11
❐
12
❐
13
❐
14
❐
15
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number. Default all Fs
❐
16
Primary Communication Format: Enter 0 - F.
❐
17
❐
18
❐
19
❐
20
Primary Account Code: Valid entries are '0 - F'. Default is '0000'.
❐
21
❐
22
❐
23
❐
24
Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
❐
25
Primary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.
❐
26
❐
27
❐
28
❐
29
❐
30
❐
31
❐
32
❐
33
❐
34
❐
35
❐
36
❐
37
❐
38
❐
39
❐
40
❐
41
Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number. Default all Fs
❐
42
Secondary Communication Format: Enter 0 - F.
❐
43
❐
44
❐
45
❐
46
Secondary Account Code: Valid entries are '0 - F'.
❐
47
❐
48
❐
49
❐
50
Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2 PM).
❐
51
Secondary Number Test Time Interval. Enter default '0' for 24 hr.; '1' for 12 hr.
❐
52
❐
53
Start Monitoring Address.
❐
54
❐
55
End Monitoring Address.
❐
56
UDACT-F Communication Selection. Enter '0' to disable UDACT-F communication; '1' for zone reporting
receive only communication; '2' for zone reporting receive/transmit communication; '3' for point reporting receive
only communication; '4' for point reporting receive/transmit communication; '5' for code wheel matching reporting,
receive only; '6' for code wheel matching point reporting, receive/transmit.
❐
57
Backup Reporting. Enter '0' to have secondary phone number act as backup only; '1' to have secondary phone
number receive all reports and messages along with primary phone number.
❐
58
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
❐
59
Make/Break Ratio. If rotary dialing is selected in Address 58; enter '0' for a 67/73 make/break ratio; '1' for a
62/38 make/break ratio.
❐
60
Leave default of '0'.
❐
61
Leave default of '0'
❐
62
AC Loss Delay. Enter '0' for no time delay after AC loss; '1' for 6 hours; '2' for 7 hours; '3' for 8 hours; '4' for
9 hours; '5' for 10 hours; '6' for 11 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for
19 hours; 'C' for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours. Default is '0'.
❐
63
Host Panel ID. Enter '0' for MS-9200; ‘2’ for Sensiscan 2000; ‘5’ for MS-9600; all other entries are invalid.
❐
64
❐
65
Loop Number for General Reports. Factory set to '00'.
❐
66
❐
67
❐
68
Sensor Number for General Reports. Factory set to '000'.
...To enter Programming Mode, press the MODE key, the code 7764 and then the [ENTER/STORE] key...