Fire-Lite UDACT-F Universal Digital Alarm Communicator Transmitter User Manual
Page 36
Programming Options
36
Document #50049 Rev.E0 1/22/01 P/N 50049:E0
Ademco Contact ID Format
If 'E' is entered for address 16, the following data is automatically programmed for the Primary phone number event
codes. Enter '000' for the data setting to disable the report.
Notes:
1.
Zero entries prevent the transmission of the report to the Central Station
2.
Refer to Contact ID program locations 64 - 68
3.
The identification of the zone/sensor number is automatically transmitted by the UDACT-F and is added to the
main event code. Refer to Table A-3, “Ademco Contact ID Reporting Structure,” on page 49, for additional
information
4.
Factory default for this report is 110 (110 is transmitted for modules, however, 111 will automatically be trans-
mitted for smoke detectors). Use Type Mode (refer to “Type Mode” on page 44) to change this report per zone
or point
TABLE 3-4:
Ademco Contact ID Primary Number
Address
Description
Setting
1
Sensor Number
69 - 71
Primary # General Alarm Code
110
000
2
72 - 74
Primary # Zone/Point Alarm Code
110
4
Note
3
75 - 77
Primary # General Supervisory Code
200
000
2
78 - 80
Primary # Zone/Point Supervisory Code
200
Note
3
81 - 83
Primary # General Fault Code
300
84 - 86
Primary # AC Fault Code
301
87 - 89
Primary # Zone/Point Fault Code
380
Note
3
90 - 92
Primary # Low Battery Fault Code
302
93 - 95
Primary # Telco Primary Line Fault Code
351
96 - 98
Primary # Telco Secondary Line Fault Code
352
99 - 101
Primary # NAC Fault Code
321
102 - 104
Primary # Communication Trouble Primary # Code
354
105 - 107
Primary # Communication Trouble Secondary # Code
354
108 - 110
Primary # 485 Communication Trouble Code
300
111 - 113
Primary # System Off Normal Code
308
114 - 116
Primary # UDACT-D Off Normal Code
350
117 - 119
Primary # System 24 Hour Test
602
120 - 122
Primary # System 24 Hour Test with Active Event
608
123 - 125
Primary # Manual Test Message
601