Normal Mode
Since higher priority events take precedence over lower priority events, the UDACT-F will transmit higher priority
events before sending the lower priority events. Priorities are as follows:
Event Activations
1.
General Alarm
2.
Zone/Point Alarm #N
3.
General Supervisory
4.
Zone/Point Supervisory #N
5.
General System Trouble
6.
AC Power Loss
7.
Zone/Point Trouble #N
8.
Low Battery
9.
Telco Primary Line Fault
10.
Telco Secondary Line Fault
11.
NAC Fault Code
12.
Communication Trouble, Primary Number
13.
Communication Trouble, Secondary Number
14.
EIA-485 Communication Bus Trouble
15.
System Off Normal Code
16.
System Automatic Test Report
17.
System Abnormal Automatic Test Report
18.
Manual Activated Test Report
Event Restorals
19.
General Alarm Restoral
20.
Zone/Point Alarm #N Restoral
21.
General Supervisory Restoral
22.
Zone/Point Supervisory #N Restoral
23.
General System Trouble Restoral
24.
AC Power Loss Restoral
25.
Zone/Point Trouble #N Restoral
26.
Low Battery Restoral
27.
Telco Primary Line Fault Restoral
28.
Telco Secondary Line Fault Restoral
29.
NAC Fault Code Restoral
30.
Communication Trouble, Primary Number Restoral
31.
Communication Trouble, Secondary Number Restoral
32.
EIA-485 Communication Bus Trouble Restoral
33.
System Off Normal Code Restoral
Note: #N represents the number of zones or devices in alarm or trouble. This is valid for all formats except
Ademco Contact ID.
For all formats, the 'general' reports are always transmitted (unless disabled). The zone or point information may fol-
low the general report if enabled.
For all pulsed formats and both Ademco Express formats, the zone/point report is repeated per the total number of
zones or points activated once factory default entries of zero are removed. See Table 3-2 on page 34, Table 3-3 on
page 35, Table 3-4 on page 36, Table 3-5 on page 37, Table 3-6 on page 38 and Table 3-7 on page 39. When Ademco
Contact ID format is used, the actual zone or point activated is identified in the report.